F112

  • Fifteen point linearization of the flow curve​
    with interpolation.
  • Flow rate:​
    seven 17mm (0.67") or 8mm (0.31") digits.
  • Total - resettable:​
    seven 17mm (0.67") digits.
  • Ambient temperature
    -40°C to +80°C (-40°F to 176°F).
Request A Quote

The F112 is a versatile flow rate indicator / transmitter and totalizer with the ability to precisely linearize the flow meter signal. In addition to the average K-Factor or Span, fifteen linearization points can be entered with their frequencies or values. The unit will interpolate between these points, greatly enhancing accuracy in any flow range, even for very low frequency applications. This linearization affects all displayed information as well as the output signals.
The display shows flow rate, total and accumulated total. On-screen engineering units are easily configured from a comprehensive selection. 

Display  
Type High intensity reflective numeric and alphanumeric LCD, UV-resistant.
Dimensions 90 x 40mm (3.5" x 1.6").
Digits Seven 17mm (0.67") and eleven 8mm (0.31") digits. Various symbols and measuring units.
Refresh rate User definable: fast, 1sec , 3sec, 15sec, 30sec, off
Option ZB  Transflective LCD with adjustable green LED backlight. Good readings in full sunlight and darkness. 
Note ZB Only available for safe area applications.
Ambient temperature  
Safe areas  -40°C to +80°C (-40°F to +176°F).
Intrinsically Safe -40°C to +70°C (-40°F to +158°F)
Power requirements  
Type PB Long life Lithium battery - life-time depends upon settings and configuration - up to 5 years.
Type PC  Intrinsically Safe long life lithium battery - life-time depends upon settings and configuration - up to 5 years.
Type PD  8 - 24V AC / DC ± 10%. Power consumption max. 10 Watt. Intrinsically Safe: 16 - 30V DC; power consumption max. 0.75 Watt.
Type PF 24V AC / DC ± 10%. Power consumption max. 15 Watt
Type PL   Input loop powered from sensor signal 4 - 20mA (type “A”) - requires types AI and OT (not Xi).
Type PM 115 - 230V AC ± 10%. Power consumption max. 15 Watt
Type PX  8 - 30V DC. Power consumption max. 0.5 Watt. 
Type ZB 12 - 24V DC ± 10% or internally powered with type PD / PF / PM. Power consumption max. 1 Watt.
Note PB/PF/PM Not available Intrinsically Safe.
Note PF/PM The total consumption of the sensor and backlight type ZB may not exceed 400mA @ 24V DC.
Note  For Intrinsically Safe applications, consult the safety values in the certificate.
Sensor excitation  
Type PB/PC/PX 3.2V DC for pulse signals and 1.2V DC for coil pick-up.
Note This is not a real sensor supply. Only suitable for sensors with a very low power consumption like coils (sine wave) and reed-switches. 
Type PD 1.2 / 3.2 / 8.2 / 12 / 24V DC - max. 50mA @ 24V DC.
Type PD-XI 1.2 / 3.2 / 8.2V DC - max. 7mA @ 8.2V DC and mains power supply voltage (as connected to terminal 1).
Note In case PD-XI and signal A or U: the sensor supply voltage is according to the power supply voltage connected to terminal 1. Also terminal 2 offers the same voltage.
Type PF / PM  1.2 / 3.2 / 8.2 / 12 / 24V DC - max. 400mA @ 24V DC.

The F-Series is your first and best choice for field mount indicators in safe and hazardous area applications. Especially in harsh weather conditions like rain, snow, salty atmosphers and temperatures between -40°C up to +80°C (-40°F up to 176°F).
Liquid flow measurement with mechanic flow meters where a precise calculation over the full measurement range is required. Also re-transmission of the flow rate and/or totalizer functions or serial communication is desired.