E018 - Explosion proof - Flow rate monitor

 

  • Speedometer​
    To indicate the actual flow rate the bargraph runs from 0 to 100% in 20 blocks, each block is 5%.
  • Refresh rate​
    User definable: 8 times/sec. - 30 secs.
  • Ambient temperature
    -40°C to +70°C (-40°F to 158°F).
Request A Quote

The E018 is one of the top models in our range of explosion proof flow computers. In addition to the average K-Factor, 16 linearization points can be entered. The unit will interpolate between these points greatly enhancing accuracy in any flow range. Moreover, a continuous flow rate monitoring feature is available with high and low flow rate alarm values and four alarm outputs. The E-series is distinguished by its high quality manufacturing and its functionality driven European design. Ruggedness and reliability is where Fluidwell stands for and it is now available in a comprehensive well designed and purpose driven Explosion proof flow monitor / totalizer 

Display 
Type

 High intensity transflective numeric and alphanumeric LCD, UV-resistant, with bi-color backlight. Red (flashing) backlight during alarm conditions. Intensity can be adjusted via the keypad. 

Note When battery powered, the backlight is only operational after a keypad touch, to extend battery lifetime.
Dimensions  Ø 65 x 45mm (2.56” x 1.77”).
Digits Seven 12mm (0.47”) and eleven 7mm (0.28”) digits. Various symbols and measuring units.
Refresh rate  User definable: 8 times/sec. - 30 secs.
Speedometer   To indicate the actual flow rate the bargraph runs from 0 to 100% in 20 blocks, each block is 5%.
Operating temperature 
Ambient -40°C to +70°C (-40°F to +158°F).
Power requirements
Type PB Long life Lithium battery - life-time depends upon settings and configuration - up to approx. 3 years.
Note PB The battery can power the backlight for a short time after a keypad touch but cannot power the relay output (OR) or the real sensor supply (Terminal P3).
Type PD 9 - 27V DC. Consumption max. 4.5W
Type PX 9 - 27V DC. Consumption max. 4.5W.
Type AH Loop powered, analog output. 11 - 27V DC, Min. 3.5mA. Consumption max. 675mW (25mA @ 27VDC).
Note AH The loop powered analog output cannot power the backlight, mechanical relay output (OR) or the real sensor supply (Terminal P3).
Sensor excitation
Type AH/PB/PX 

 Terminal S3: 3V DC for pulse signals and 1.2V DC for coil pick-up, Iout max. 100μA.

Note This is not a real sensor supply. Only suitable for sensors with a very low power consumption like coils (sine wave) and reed-switches.
Type PD Terminal P3: 8.2 / 12 / 24V DC 8.2V DC, Iout max. 20mA. 12V DC, Iout max. 30mA. 24V DC, Iout max. 75mA (this voltage varies depending on the input supply voltage)
Terminal connections
Type Removable plug-in terminal strip. Wire max. 1.5mm2 and 2.5mm2 .
Data protection
Type EEPROM backup of all settings. Backup of running totals every minute. Data retention at least 10 years.
Pass-code Configuration settings can be pass-code protected.
Directives & Standards
EMC Directive 2004/108/EC, FCC 47 CFR part 15.
Low voltage  Directive 2006/95/EC.
ATEX / IECEx  Directive 94/9/EC, IEC 60079-0, IEC 60079-1, IEC 60079-31.
CSA CSA 22.2 No. 25, No. 30.
IP & NEMA  EN 60529 & NEMA 250.

Flow measurement in an explosion proof application with mechanical flow meters, where re-transmission of the totalizer, monitoring of the flow rate and HART communication is required.
The E018 offers you a flow rate monitor / totalizer designed to be used in rough and tough applications, beyond being just explosion proof. Its sturdy design and ease of use are unequaled by any other explosion proof indicator in the market! The E-Series is always your first and safest choice in explosion proof applications.