E110 - Explosion proof - Flow rate indicator
- Speedometer
To indicate the actual flow rate the bargraph runs from 0 to 100% in 20 blocks, each block is 5%. - Refresh rate
User definable: 8 times/sec. - 30 secs. - Digits
Seven 12mm (0.47”) and eleven 7mm (0.28”) digits. Various symbols and measuring units.
The E110 is a popular model in our range of explosion proof flow rate indicators, complete with pulse and analog output signals. The E-series is distinguished by its high quality manufacturing and its functionality driven European design. We believe, it is not just about fulfilling the requirements for explosion proof, but it is about safety during daily operation. Ruggedness and reliability is where Fluidwell stands for and it is now available in a comprehensive well designed and purpose driven explosion proof flow rate indicator / totalizer.
Display | |
---|---|
Type |
High intensity transflective numeric and alphanumeric LCD, UV-resistant, with bright backlight. Intensity can be adjusted via the keypad. |
Note | When battery powered, the backlight is only operational after a keypad touch to extend the battery lifetime. |
Dimensions | Ø 65 x 45mm (2.56” x 1.77”). |
Digits | Seven 12mm (0.47”) and eleven 7mm (0.28”) digits. Various symbols and measuring units. |
Refresh rate | User definable: 8 times/sec. - 30 secs. |
Speedometer | To indicate the actual flow rate the bargraph runs from 0 to 100% in 20 blocks, each block is 5%. |
Operating temperature | |
Ambient | -40°C to +70°C (-40°F to +158°F). |
Power requirements | |
Type PB | Long life Lithium battery - life-time depends upon settings and configuration - up to approx. 3 years. |
Note PB | The battery can power the backlight for a short time after a keypad touch but cannot power the relay output (OR) or the real sensor supply (Terminal P3). |
Type PD | 9 - 27V DC. Consumption max. 4.5W |
Type PX | 9 - 27V DC. Consumption max. 4.5W. |
Type AH | Loop powered, analog output. 11 - 27V DC, Min. 3.5mA. Consumption max. 675mW (25mA @ 27VDC). |
Note AH | The loop powered analog output cannot power the backlight, mechanical relay output (OR) or the real sensor supply (Terminal P3). |
Sensor excitation | |
---|---|
Type AH/PB/PX |
Terminal S3: 3V DC for pulse signals and 1.2V DC for coil pick-up, Iout max. 100μA. |
Note | This is not a real sensor supply. Only suitable for sensors with a very low power consumption like coils (sine wave) and reed-switches. |
Type PD |
Terminal P3: 8.2 / 12 / 24V DC 8.2V DC, Iout max. 20mA. 12V DC, Iout max. 30mA. 24V DC, Iout max. 75mA (this voltage varies depending on the input supply voltage) |
Terminal connections | |
Type | Removable plug-in terminal strip. Wire max. 1.5mm2 and 2.5mm2 . |
Data protection | |
Type | EEPROM backup of all settings. Backup of running totals every minute. Data retention at least 10 years. |
Pass-code | Configuration settings can be pass-code protected. |
Directives & Standards | |
EMC | Directive 2004/108/EC, FCC 47 CFR part 15. |
Low voltage | Directive 2006/95/EC. |
ATEX / IECEx | Directive 94/9/EC, IEC 60079-0, IEC 60079-1, IEC 60079-31. |
CSA | CSA 22.2 No. 25, No. 30. |
IP & NEMA | EN 60529 & NEMA 250. |
Liquid flow measurement where re-transmission of the flow rate and/or totalizer functions or serial communication is required.
The E110 offers you a flow rate indicator / totalizer designed to be used in rough and tough applications, beyond being just explosion proof. Its sturdy design and ease of use are unequaled by any other explosion proof indicator in the market! The E-Series is always your first and safest choice in explosion proof applications.