Impeller Hot tap flow sensor Models 225BR/226BR/226SS
- Pipe size range
3” up to 48” - Pressure ratings for 225BR
At 24°C 300 psi, At 135°C 210 psi - Pressure ratings for 226BR
At 24°C 400 psi, At 135°C 250 psi - Pressure ratings for 226SS
At 24°C 400 psi, At 135°C 300 psi
The series 200 flow sensors feature a six bladed impeller design with a proprietary non-magnetic sensing mechanism. The forward swept impeller shape provides higher, more consistent torque and is less prone to be fouled by water borne debris. The forward curved shape coupled with the absence of magnetic drag provides improved operation and repeatability even at lower flow rates.
The model 225BR and 226BR/226SS sensors are used for flow measuring applications in most metallic or non-metallic pipes where it would be difficult to shut down or drain the line for installation or service. The model 225 features agate valve for isolation and the model 226 a ball valve. If the pipe is too hot tapped, the ball valve is recommended
General Specification | |
---|---|
Temperature ratings |
Standard version: 105°C (221°F) continuous service Irrigation version: 66°C (150°F) High temperature version: 140.6°C (285°F) continuous service, 150°C (305°F) peak temperature (limited duration) |
Pressure ratings for 225BR |
- At 24°C 300 psi - At 135°C 210 psi |
Pressure ratings for 226BR |
- At 24°C 400 psi - At 135°C 250 psi |
Pressure ratings for 226SS |
- At 24°C 400 psi - At 135°C 300 psi |
Pipe size range | 3” up to 40” |
Recommended design flow range |
0,1 to 9 m/s Initial detection below 0,1 m/s |
Accuracy |
±1.0% of full scale over recommended design flow range
±4.0% of reading within calibration range
|
Repeatability |
±0.3% of full scale over recommended design flow range
|
Linearity |
±0.2% of full scale over recommended design flow range
|
Output frequency | 3.2 Hz to 200 Hz |
Output pulse width |
5 msec ±25%
|
Electrical cable for standard sensor electronics | 6 m of 2-conductor 20 AWG shielded U.L. type PTLC wire provided for connection to display or analog transmitter unit.Rated to 105°C. May be extended to a maximum of 600 m with similar cable and insulation appropriate for application
|
Electrical cable for IR sensor electronics | 1,2 m of U.L. style 116666 copper solid AWG 18 wire with direct burial insulation Rated to 105°C. |
Sensor sleeve and hex adapter for 225BR and 226BR | Sleeve: Admiralty brass, UNS C44300; hex adapter: valve bronze, UNS C83600 |
Sensor sleeve and hex adapter for 226SS | 316 series stainless steel |
- Water application