M853 Data Acquisition & Communication Module
- Modem Communication
2G, 3G and 4G - Easy Installation
Flexible mounting option: Wall/Panel/Pipe - Data Logging
20 million data enteries with date & time stamp
M853 is an ultra-low power “all-in-one” Data Acquisition & Communication Module including datalogging, designed for a wide-range industrial applications. The M853 can be fully configured according to your process requirements. No additional signal converters / amplifiers, encapsulating cabinet or other electrical installation material necessary. Shortly: As long as your sensor, instrument, (field)device or other equipment has an analog output, you can take advantage of ProcessMonitor.
The M853 is in full compliance with the ProcessMonitor Webportal or ProcessView stand-alone software package for visualization, data history, trend graphics and/or extensive alarming.
Technical Specification | |
---|---|
Power Supply |
Type PB D-Size Long-life 3.6V Lithium battery with smart Type 3PB 3 x D-size Long-life 3.6V Lithium battery with Type PD 8 - 30V DC adapter, with integrated battery Type PS Solar powered and 3xAA NiMH rechargeable Consumption < 110 µA @ 3.6V in sleep mode.
|
Sensor excitation | Power switch For low power applications: 200mA @ 12V DC |
Enclosure | General UV stabilized Polycarbonate. Sealing EPDM. Classification IP68 (30 min.@2 meters). Dimensions 130 x 120 x 85mm (5.12” x 4.72” x 3.35”) - W x H x D. Weight approximately 530 gr. Cable entry No holes. |
Terminal connections | Removable plug-in terminal strip. Wire max. 1.5mm2. |
Operating temperature | -30°C to +75°C (-22°F to +167°F) |
Digital inputs |
Status / pulse inputs 3 status or counter/pulse inputs 0 ~ 3.6 Volts, TTL. |
Analog inputs |
Inputs 2 x current loop inputs |
Communication (optional) |
Function Input expansion and flexibility. |
Local configuration |
Function Configuring all settings before operation. |
Data logging | Storage Standard 4GB micro-SD card. Frequency Independent regular and alarm intervals; 1 second to 1 day intervals. Data entries Over 20.000.000 with date and time stamp. Log file FAT32 file system, readable with any text editor |
Data communication outputs | Frequency Independent regular and alarm intervals; 1 second to 1 day intervals Direct push on alarm raise and fall. Operation Free configurable daily operation time bracket (e.g. 07.00AM to 08.00PM). Alarming SMS to 1 number direct from M853 or extensive alarm capabilities by SMS and Email in combination with the ProcessMonitor CloudPortal. Format Native TXT, JSON or CSV log files. Transmit HTTP, FTP, Email (SMTP) or TCP (CHAP). |
Alarm output |
Function Transmitting alarm status. |
Modem communication |
2G, 3G and 4G SIM-card 2FF (class B) SIM-card slot. Antenna Integrated. External antenna optional available. |
Specially designed for industrial applications using (field) devices and instrumentation to measure level, flow, weight/mass, pressure, temperature, dissolved oxygen, pH, conductivity, vibration, energy/fuel consumption etc.
Extremely suitable for replenishment purposes or logistic and Supply Chain (SCM) optimization for raw bulk materials including: Remote Silo/Tank Monitoring, Remote Inventory Management, Customer and Vendor Managed Inventory (VMI).